The 240.4(B) 'next size up' rule allows rounding up the overcurrent device only up to what rating?

800A or less and three conditions must be met.

Start playing free

  1. 100A or less
  2. 800A or less ✔
  3. 2,000A or less

Why: If a conductor's ampacity doesn't match a standard breaker size, 240.4(B) lets you use the next higher standard rating. This works only at 800A or less and only when three conditions are met.

Huh, didn't know that: Above 800A, conductor ampacity must be at least the overcurrent device rating, per 240.4(C).

The dad joke
Why did the breaker want a bigger size? It needed some room to grow.
Like this card?
Play the game

References

Answer: 800A or less. If a conductor's ampacity doesn't match a standard breaker size, 240.4(B) lets you use the next higher standard rating. This works only at 800A or less and only when three conditions are met.

  1. EC&M: Protecting Conductors Part 3 www.ecmweb.com/maintenance-repair-operations/article/20901392/protecting-conductors-part-3
    if you’re working with 800A or less, you can use the next higher standard OCPD if you meet three conditions [240.4(B)]